The SensorLink module, combined with a CT, intelligently analyzes thermal runaway trend and effectively alarms for battery thermal runaway with detailed reporting to the Gerchamp Nexus.

Distributed single module architecture design, one module for one string
Float current and ambient temperature monitoring
Cell internal resistance monitoring
Thermal runaway trend Intelligent analyses and alarm
UART*2 communication port, MODBUS/RTU protocol


Product Components


BattLink

One BattLink can monitor the voltage, internal resistance and negative pole temperature of a single battery to provide continuous 24/7 monitoring of your battery infrastructure.

SensorLink

One module with an additional CT per battery string will intelligently analyze thermal runaway trends and effectively produce alarms for battery thermal runaway.

CurrentLink

One module with an additional CT per battery string will monitor the charge/discharge current and ambient temperature of a string.

Nexus

It can manage up to six groups of batteries, each group has a maximum of 300, and the total number is up to 960, with display and buttons.



Battery Health Indicators


The SensorLink module monitors a variety of battery health indicators of a given battery string and reports back to the Nexus module. When combined with the other modules of the battery monitoring system, it ensures uptime with 24/7 monitoring of batteries in all applications.

Float Current

Ambient Temperature

Thermal Runaway Trend

Intelligent Analysis

Alarms



Design and Appearance


SensorLink Module Appearance

Name Description
Power Input 10.8~13.8VDC input, powered by control module or externally.
Communication Port UART port, dual-channel, internal parallel connection, connecting to the Nexus control module.
Float Current 1 & Ambient Temperature Port Connect to the float current transformer through the float current test cable and monitor 1 float current.
The test cable has 2 environmental temperature monitoring probes.
Float Current 2 Port Connect to the float current transformer through the float current test cable and monitor 1 float current.
Float Current 3 Port Connect to the float current transformer through the float current test cable and monitor 1 float current.
Indicator Lights There is a two-color indicator light that indicates four things based on the below presentation.

GREEN LIGHT ON:

The module is powered on.

GREEN LIGHT FLASHES ONCE:

There is a module hardware fault/an abnormal internal resistance test.

RED LIGHT ON:

The internal resistance is normal.

RED LIGHT FLASHES ONCE:

The communication is normal.

Communication Ports
COM1 and COM2 are in internal parallel

Pin Definition Description
1 GND Signal ground
2 RX UART receive
3 TX UART send
4 GND Signal ground

Power Input

Pin Definition Description
1 + DC12V+
2 - DC12V-

Float Current & Temperature Port (J1)

Pin Definition Description
1 T1 Ambient Temperature 1
2 T1 Ambient Temperature 1
3 T2 Ambient Temperature 2
4 T2 Ambient Temperature 2
5 GND Connect to float current hall sensor
6 M Connect to float current hall sensor
7 -15V Connect to float current hall sensor
8 +15V Connect to float current hall sensor

Float Current Power Input (J2/J3)

Pin Definition Description
1 GND Connect to float current hall sensor.
2 M Connect to float current hall sensor.
3 -15V Connect to float current hall sensor.
4 +15V Connect to float current hall sensor.